AC short cycling
Video
Checklist
What I see
Trane outdoor unit with spine-fin coil, probes connected, and visibly dirty coil. Pressure behavior indicates low-pressure protection trip after startup.
Safety first
Panel is open with live high-voltage components. Keep clear of contactor and capacitor terminals, fan blade, and avoid refrigerant venting while handling probes.
Diagnosis + next steps
- 1Confirm diagnosisLow suction + low head + near-zero subcooling indicates severe loss of charge, not restriction.
- 2Leak search outdoor firstInspect spine-fin rub points and accumulator underside for oil marks/shiners.
- 3Then inspect indoor evaporatorIf outdoor is clear, move to evap coil as common leak source.
- 4Pressure test properlyRecover charge and perform standing nitrogen pressure test (300+ PSI) to locate leak.
Watch for
Standing pressure only means some refrigerant is present, not that charge is correct. Do not top off before locating and repairing the leak source.